Front | Back |
AUTOMATIC PRESSURE MAINTENANCE DEVICE
|
Maintains pneumatic pressure on the piping system set to specific limits by controlling a plant air system. a single air compressor, or a nitrogen supply.
|
AUTOMATIC WET SPRINKLER SYSTEM
ANTIFREEZE SPRINKLER SYSTEM: |
The freezing point of solutions in antifreeze shall be tested annually by measuring the specific gravity with a hydrometer or refractometer and adjusting the solutions if necessary. Annual testing must be performed in accordance with NFPA 25/2011.
|
COLOR CODED
FIRE DEPARTMENT FOAM CONNECTION: |
RED with contrasting BRIGHT ORANGE band or caps. A durable sign that reads: "CHEMICAL FOAM DIRECT TO TANKS" or "3% MECHANICAL FOAM SOLUTION DIRECT TO TANKS", shall be conspicuously posted immediately adjacent to such connections.
|
COLOR CODED
FIRE DEPARTMENT WATER CONNECTIONS: |
RED. A durable sign that reads: "WATER FOR FOAM SYSTEM", shall be conspicuously posted immediately adjacent to such connections.
|
COLOR CODED
PIPING, VALVE BODIES AND HANDLES: |
RED with contrasting BRIGHT ORANGE bands
|
CONTROL VALVES
SYSTEM CONTROL VALVE SIGNAGE: |
A sign identifying the location of the sidewalk box housing the sprinkler system control valve shall be conspicuously posted on the exterior wall of the building directly opposite the sidewalk box.
|
CRITICAL DEFICIENCY
|
A deficiency that if not corrected, can have an effect on the performance of the fire protection system.
|
FIRE DEPARTMENT CONNECTIONS:
|
Fire Department Connections must always be accessible. A working space of not less than 36 inches in width, 36 inches in depth and 78 inches in height shall be provided and maintained.
|
FIRE PUMP, LIMITED SERVICE
|
A fire pump with a motor rating not exceeding 30 hp and utilizing a limited service fire pump controller.
|
FIRE PUMP, AUTOMATIC STANDPIPE
|
A fire pump located at or below street level that supplies the lower 300 feet (91.4m) of a standpipe system or a combined standpipe and sprinkler system.
|
FIRE PUMP, FOAM
|
A fire pump used to boost water supply pressures in a fire protection system where such system uses firefighting foam as an additive.
|
FIRE PUMP, SPECIAL SERVICE
|
A fire pump that is located above street level and that receives its water supply from a gravity tank or suction tank.
|
FIRE PUMP, SPRINKLER BOOSTER PUMP
|
A fire pump that supplies sprinkler systems only.
|
FIRE PUMP, WATER MIST SYSTEM
|
A fire pump used to boost water supply pressures in a fire protection system where such system utilizes water misting technology.
|
FOAM - WATER SPRINKLER AND SPRAY COMPONENTS
FOAM CONCENTRATE PROPORTIONING: |
Positive pressure or balanced pressure injection are the preferred methods of supplying foam concentrates into the water flowing through the supplying piping.
|