Front | Back |
Minimum exit door width.
|
0.71 mtr.
|
Minimum floor to ceiling height.
|
2.30 mts.
|
Maximum stair rise height for a class A stair.
|
0.19 mtr.
|
Maximum height between landings for class A stair.
|
2.75 mts.
|
Minimum headroom for class A & B stairs.
|
2.00 mts.
|
Unit area per person for waiting areas or standing rooms.
|
0.28 sqm.
|
Number of exits for place of assembly for 1000 occupants
|
4
|
Travel distance to an exit without fire sprinkler system
|
46.00 mts.
|
Travel distance to an exit with fire sprinkler system.
|
61.00 mts.
|
Minimum spacing of rows of seats from back to back for a public assembly building.
|
0.83 mtr.
|
Maximum number of seats in a row in between aisles.
|
14
|
Maximum number of seats in a row opening on to an aisle at one side.
|
7
|
Standard width of a seat without dividing arms for places of assembly.
|
60 cms.
|
Minimum width of an aisle serving an occupant of 60 |
91 cms.
|
Minimum headroom created by any projection from the ceiling
|
2.00 mts.
|